TABLE 1A — CABLE RANGE
Model – Frame Size 3 | Nominal Cable Outer Diameter (OD) 1 | |||
2 or 3 Cables (no liner) 2 | 1 – Cable (no liner) 2 | |||
Min Cable OD mm (in) |
Max Cable OD mm (in) |
Min Cable OD mm (in) |
Max Cable OD mm (in) |
|
T3-03 | 30.0 (1.18) | 39.0 (1.54) | 47.0 (1.85) | 57.0 (2.24) |
T3-04 | 37.0 (1.46) | 47.0 (1.85) | 57.0 (2.24) | 70.0 (2.76) |
T3-05 | 45.0 (1.77) | 58.0 (2.28) | 70.0 (2.76) | 86.0 (3.39) |
T3-06 | 56.0 (2.20) | 71.0 (2.80) | 86.0 (3.39) | 106.0 (4.17) |
Notes to Table 1A:
- The dimensions listed in the cable range represent the diameter across the outermost layer of each cable (e.g. outer sheath). For application assistance with other cable configurations, contact Talon Products.
- In addition to securing three cables, Talon T3 cable cleats may be used to secure two cables positioned side-by-side (i.e. no cable in the upper position), or a single cable.
- Other Talon cable cleat frame sizes are available on request.
TABLE 1B — DIMENSIONS
Model – Frame Size | H1 1 mm (in) |
H2 (Min/ Max) 1, 2 mm (in) |
H3 (Min/ Max) 1, 2 mm (in) |
W 1 mm (in) |
ØD 1 mm (in) |
B 1 mm (in) |
T3-03 | 90.9 (3.58) | 75.1 (2.96) | 116.1 (4.57) | 130.5 (5.14) | Qty-1 | N/A |
91.9 (3.62) | 132.9 (5.23) | 10.2 (0.40) | ||||
T3-04 | 105.1 (4.14) | 86.3 (3.40) | 127.3 (5.01) | 147.8 (5.82) | Qty-2 | 34.0 (1.34) |
107.8 (4.24) | 148.9 (5.86) | 10.2 (0.40) | ||||
T3-05 | 108.0 (4.25) | 101.4 (3.99) | 142.4 (5.60) | 168.4 (6.63) | 40.0 (1.57) | |
127.9 (5.03) | 168.9 (6.65) | |||||
T3-06 | 123.5 (4.86) | 120.1 (4.73) | 161.1 (6.34) | 197.4 (7.77) | 36.0 (1.42) | |
152.6 (6.01) | 193.6 (7.62) |
Notes to Table 1B:
- Dimensions:
- H1 = Height of base (to top of gripping hardware)
- H2 = Height above rung (i.e. from bottom of cable)
- H3 = Overall height
- W = Overall width
- ØD = Auxiliary mounting hole(s) quantity & inside diameter
- B = Mounting hole spacing
- “Min” represents the nominal dimension of a Talon cable cleat securing three of the smallest cables in the cable range. “Max” represents the nominal dimension of a Talon cable cleat securing three of the largest cables in the cable range. For other dimensions, contact Talon Products.
- For mounting information, refer to the Talon T3 Cable Cleat Installation Guide.
TABLE 2 — PART NUMBER 1, 2, 9
Model 3 | – | Frame Size 4 | – | Frame Type 5 | Integral Gripping Hardware 6 | Rung Spacer 7 | – | Options and Custom Features 8 |
T3 | – | 03 * 04 * 05 * 06 * 07 08 09 |
– | F0 = Samples Only F1 = Heavy Duty F2 = Standard Duty |
H4 = 304 S/S Bolts and Flange Nuts H6 = 316 S/S Bolts and Flange Nuts |
R00 R10 R15 R20 R30 R40 |
– | 000 = Standard Product (no custom features) |
Notes to Table 2:
- Talon® cable cleat part numbers consist of 17 characters, including 3 dashes. Asterisks are for information only and are not included in the part number.
- * = Talon® cable cleat frame sizes normally in stock and available through Talon Products’ Rapid Ship Program.
- Talon® cable cleats have passed rigorous 3rd party testing in accordance with ASTM B117, IEC 60695, IEC 61914, ISO 4892-2, UL 94, UL 969 and UL 2239.
- Talon® cable cleats are molded from high-strength polyamide that is electrically insulating, flame resistant, UV resistant, low smoke, zero-halogen and resistant to drilling mud, gaseous atmospheres, salts and many other chemicals.
- Talon® cable cleats secure cables subject to lateral and torsional forces and provide axial strain relief for vertical and horizontal cables. Additionally, Talon® cable cleats utilizing the F1 heavy duty frame are designed and tested to protect cables from mechanical damage resulting from short circuits. Talon® cable cleats utilizing the F0 frame are product samples only and may not be placed into service. Talon® cable cleats may be used with high voltage, medium voltage and low voltage cables.
- Talon® cable cleats include integral stainless steel gripping bolts that are held captive in the base for ease of installation. Talon® cable cleats typically do not require additional mounting hardware when simultaneously enclosing cables and their support rung (i.e. in ladder-type cable tray). For wall mounting or other mounting preferences, auxiliary mounting hole(s) are included in the base. Mounting hardware for wall mounting or other mounting preferences is customer furnished.
- Talon® cable cleats accommodate box, elliptical, hat, I-beam, oval, rectangular, round, square and channel strut rung profiles from most ladder-type cable tray manufacturers. Unless “R00” is specified, each Talon® cable cleat includes an adhesive-backed neoprene rung spacer that compresses slightly during installation. Refer to Table 3 for rung spacer selection. For mounting information, refer to the Talon® T3 Cable Cleat Installation Guide.
- “000” = Standard product (no custom features required). Other 3-digit Custom Feature part numbers are assigned by Talon Products.
- Examples:
- Qty-3 x 35.0 mm (1.38 in) OD cables in ladder-type cable tray with 28.6 mm (1.125 in) deep rungs; subject to fault current
Purchase part number → T3-03-F1H4R00-000 - Qty-2 x 41 mm (1.61 in) OD cables in ladder-type cable tray with 25.4 mm (1.0 in) deep rungs; not subject to fault current
Purchase part number → T3-04-F1H4R10-000 or T3-04-F2H4R10-000 - Qty-1 x 85 mm (3.35 in) OD cable in ladder-type cable tray with 22.2 mm (0.87 in) deep rungs; subject to fault current
Purchase part number → T3-05-F1H4R20-000
- Qty-3 x 35.0 mm (1.38 in) OD cables in ladder-type cable tray with 28.6 mm (1.125 in) deep rungs; subject to fault current
TABLE 3 — RUNG SPACER SELECTION 1
Rung/ Strut Depth 2, 3 mm (in) |
Rung/ Strut Width 4 mm (in) |
Example Ladder-type Cable Trays 5 | Part Number |
> 27.4 (1.08) | ≤ 45.7 (1.8) | US Tray (standard & strut rung) | R00 (not req’d) |
24.5 – 27.4 (0.96 – 1.08) | Basor Basortrav IL; B-Line Series 2-5; Cablofil Itray; Enduro (std rung); PW (box rung) | R10 | |
22.8 – 24.4 (0.90 – 0.96) | T&B (aluminum & steel strut rung) | R15 | |
21.0 – 22.7 (0.83 – 0.89) | Cope Ladder (swage rung) | R20 | |
18.9 – 20.9 (0.74 – 0.82) | B-Line IEC Ladder; Code Electric (aluminum narrow rung) | R30 | |
15.0 – 18.8 (0.59 – 0.74) | MP Husky Flange Out (box rung); Zip Tray Series BW, BX, BY, BZ | R40 |
Notes to Table 3:
- Rung spacers are utilized for rungs or strut profiles with depth ≤ 27.4 mm (1.08 in).
- For rung or strut depth > 28.6 mm (1.125 in), secure cable cleat to top of rung or strut and select R00 part number.
- For rung or strut depth < 15.0 mm (0.59 in), contact Talon Products.
- For rung or strut width > 45.7 mm (1.8 in), secure cable cleat to top of rung or strut and select R00 part number.
- For other cable tray brands and models, correlate the rung dimensions to the respective rung spacer or contact Talon Products.
TABLE 4 — CLASSIFICATIONS and TYPICAL TEST RESULTS 1
Category | Classification |
Color | Permanent Black (F1 & F2 Frames) |
Strength Class (§9.1.a) | Rigid — Cable cleats intact (no deformation after lateral retention test or short circuit tests) |
Material Class (§6.1.3) | Composite – Nonmetallic frame and stainless steel gripping bolts |
Ambient Temperature for Permanent Application (§6.2) | -60° C to +90° C (-76° F to +194° F) — Suitable for 250° C momentary conductor temperature |
Impact Resistance at Low Temperature (§6.3.5, §9.1.b, §9.2) | Very Heavy, 20 J Impact Energy @ -60° C (-76° F) — Performed on UV test specimens |
Lateral Retention at High Temperature (§6.4.2, §9.1.c, §9.3) | > 17,000 N (3,822 lbf) @ +60° C (140° F) — Parallel or perpendicular to mounting surface |
Axial Retention at High Temperature (§6.4.3, §9.1.d, §9.4) | 5,000 N (1,124 lbf) @ +60° C (140° F) — Performed on short circuit test specimens |
Resistant to Electromechanical Forces — F1 Frame (§6.4.5, §9.1.e, §9.5) |
Trefoil: 154 kAPEAK (Ø33.2 mm cables) — Specimens subsequently tested for axial retention |
Cable cleats, cables and cable tray intact and reusable after multiple short circuit tests | |
Resistant to Environmental Influences (§6.5) | Resistant to UV Light (§6.5.1.2, §11.1) — Specimens subsequently tested for impact resistance |
High Corrosion Resistance (§6.5.2.2, §11.2) — Suitable for outdoor and wet locations | |
Resistant to Flame Propagation (§10.1) | Pass – Exceeds Test Criteria – No flaming, no dripping and no ignition of paper |
Low Smoke Emission (§10.2) | Pass – Exceeds Test Criteria – Low smoke zero-halogen resin |
Notes to Table 4:
- Section numbers refer to international standard IEC 61914:2015, Cable Cleats for Electrical Installations.